Welcome to IML Welcome to IML
 
EDR-101 Delayed Egress Control Panel - with Keypad Console, Dual Tone (Fire/Exit) Audible Alert, 3 Second Nuisance/ 15 Second Alarm Delay, Programmable Clock/Day Scheduler, 3 Status Outputs, Programmable Escort Code for Keypad (Or Optional Key Switch)

Part#: DRT7101-P
Hot#: 182063

Available: 1 ( 1 KAN )

  • Series Overview
  • Specifications
Notice: The info below is not item specific.

Dortronics Systems, Inc.


When armed, the EDR 101 panel is activated in one of 2 ways. One utilizing a door mounted egress bar with internal activating switch; (#6420xS25). The other by utilizing the attempted egress switch option which is a component mounted on the maglock; (XEDR). Applying a continual pressure of 15 pounds or more on the emergency egress bar (#6420xS25) or pushing directly door (XEDR) for three seconds begins the sequence. The 3 second period is a nuisance delay to prevent an accidental alarm if someone were to bump into the door inadvertently. Once activated, the alarm will sound and the red LED will flash until the system is manually reset by entering the designated code using the keypad.

Features:

  • EDR System 101: A complete system includes the controller, power supply, lock, door position switch and an egress activation device.
  • Conforms to All Life Safety Codes: The 7101 delayed egress system performs all functions required by NFPA-101 life safety code.
  • Authorized Access/Escort Egress: A delay override feature allows an authorized individual immediate access without alarm using the onboard keypad. The controller contains an input for a remote keypad or other secure device such as a key switch or card reader which may be incorporated for after hours access.
  • Automatic Anti-Tailgate Re-Lock: The door status switch monitors door position in both the armed and disarmed states. This allows the immediate re-lock and rearming of the door after an authorized passage during an armed time schedule.
  • Remote Monitoring and Control: Door release and alarm shunt capability from a remote guard station is possible when used with the 7600 series annunciator/controller. Relay outputs are provided for electric locks, auxiliary alarms, and to allow integration with any card access control, CCTV monitoring system, or other security control devices.
  • Built-In Nuisance Delay: The three second nuisance delay prevents inadvertent alarming of the door. After three seconds of continuous activation, the EDR System 101 controller enters an irreversible unlock sequence. An audible warning is activated as the countdown begins.
  • Programmable Clock /Calendar: Door armed and door unlocked intervals can be scheduled by time of day and by the day of the week. Programmable arm and disarm intervals allow unique week day and weekend schedules or total lock down 24 hours per day, seven days a week.
  • Adjustable Volume Control: Settings are selectable on the back of the panel to control the volume level. HI, LO or mute can be easily selected via switch position.
  • NFPA 101/BOCA code compatible
  • 15 or 30 Second egress delay
  • Built-in keypad access control
  • Anti-tailgate re-locking
  • Selectable volume control

Specifications:

  • EDR System 10l Control Panel: This 3- gang panel with keypad, LEDs, and sounder is typically mounted, adjacent to the door on the secured side. The stainless steel panel can be recessed flush or installed using the beige surface box.
    • 4012: (EDR) Power Supply - 12 volt DC 1 amp plug-in power supply (included with each EDR 101 controller above).
    • 1107xEDR: 600 lb. magnetic lock with onboard door position switch and attempted egress switch.
    • 1110xEDR: 1200 lb. magnetic lock with onboard door position switch and attempted egress switch.
  • Unique Access/Escort Codes: The master and secondary codes are field programmable to limit door unlocking to authorized personnel only. The secondary access code may be changed at any time without affecting the master code users.

Specifications for Dortronics Systems, Inc. DRT7101-P

Other Specs
Alternate Codes7101-P, 7101P
CategoryAccess Control, Access Management, Hardwired