Power Supply/Charger Board Only, Output 24VDC @ 10 Amp, Single Filtered and Electronically Regulated Output, Aux Output, FAI Fire Alarm Interface, LinQ2 Ready, Input: 115VAC, LED Visual Indicators
Part#: ALXEFLOW104NB
Hot#: 173842
Mfg: Altronix
Available: 79 ( 8 DAL, 4 DEN, 19 KAN, 8 LA, 2 LV, 8 SAC, 14 SEA, 12 SLC, 4 STX )
Notice: The info below is not item specific.
Altronix
EFLOW104NB UL Listed Sub-Assembly power supply/charger converts a 120VAC, 60Hz input into a single 24VDC output. It also offers a suite of Features that includes fire alarm disconnect, overvoltage protection, and low power disconnect which prevents deep discharge of stand-by batteries.
Features:
- UL Listed For: Access Control System Units (UL294).
- UL Listed For: Power Supplies for use with Burglar Alarm Systems (UL603).
- UL Listed For: Power Supplies for Fire Protective Signaling Systems (UL1481).
- cUL Listed For: CSA Standard C22.2 No.205-M1983, Signal Equipment.
- cUL Listed For: CAN/ULC - s319-05, Electronic Access Control Systems.
- cUL Listed For: ULC-S318-96 - Power Supplies for Burglar Alarm Systems. Also suitable for Access Control.
Specifications:
- Input:
- Voltage: 120VAC, 60Hz, 4.5A max.
- Fusing: 6.3A / 250V.
- Outputs:
- Voltage: 24VDC.
- Current: 10A continuous max.
- Auxiliary: Power-limited @ 1A (unswitched).
- Other: Overvoltage protection. Filtered and regulated.
- Back-up Battery: (not included).
- Type: Sealed lead acid or gel type.
- Fuse: Rating 15A @ 32VDC.
- Failover: Upon AC loss, instantaneous.
- Fire Alarm Disconnect:
- Supervised: Latching or non-latching.
- EOL: 10K Resistor.
- Supervision:
- AC Failure: Form “C” contacts.
- Battery: Form “C” contacts.
- Low DC Power Shutdown: Shuts down DC output terminals if battery voltage drops below 71-73% for 12V units and 70-75% for 24V units depending on the power supply). Prevents deep battery discharge.
- Indicators (LED):
- Input: 120VAC is present.
- DC Output: Powered.
- Agency Listings:
- UL Access Control: UL294.
- UL Burglar Alarm: UL603.
- UL Fire Alarm: UL1481.
- cUL Burglar Alarm: ULC-S318-96.
- cUL Access Control: ULC-S319-05.
- cUL Signal Equipment: CSA C22.2 No.205.
- Dimensions (L x W x H):
- 8.25"(209.5mm) x 4.56"(115.8mm) x 1.5"(38.1mm).
- Product Weight:
- 1.1 lbs. (0.5 kg).
- Temperature:
- Operating: 0°C to 49°C (32°F to 120°F).
- Storage: - 20°C to 70°C (- 4°F to 158°F).
- Relative Humidity:
- 85% +/- 5%
- BTU/Hr. (approx.):
- 123 BTU/Hr.
Specifications for Altronix ALXEFLOW104NB
Other SpecsAlternate Codes | EFLOW104NB |
Category | Access Control, Alarm Power Supplies, Alarms & Intercom, Burglar Alarms, CCTV Products, Power Supplies, Wire & Power Supplies |