Power Distribution Board, 8 Glass Fused Output, Fire Trigger/Relay, 1 Amp, 12/24VDC, 8 Amp Transfer Relay, UL
Part#: SMCPDB-8F1R1
Hot#: 159579
Mfg: Securitron
Available: 10 ( 6 LA, 2 PHX, 2 SLC )
Notice: The info below is not item specific.
Securitron
The PDB-8C1R /8F1R power distribution control interface converts a main non-power limited DC power source to 8 power-limited outputs that can be controlled by a fire alarm control panel. Each output can be selectively set to turn on or to turn off when triggered by the panel. The system can interface to the PDB-8C1R /8F1R with either of two or both supervised trigger inputs.
Features:
- 8 Power limited outputs with auto-resetting
- Circuit breakers for model 8C1R
- Each output is individually selectable to turn on, turn off, or always on when triggered
- Outputs can be triggered with: Voltage or reverse polarity (optically isolated) N/O or N/C switch with supervised EOL
- Form C contacts (triggered) and red LED (TRG) indicate trigger status
- Form C contacts (trouble) and green LED (TRB) indicate: One of the output circuit breakers is tripped main fuse blown or no power on input
- Operates with 12-28VDC; nominal 12-24VDC
- Each output pair has a removable terminal block and green status LED
- Main power has green status LED
- UL Listed sub assembly for access control and burglar alarm systems
Specifications:
- Input Voltage: 12-28 VDC (nominal 12-24 VDC)
- Output Voltage: 11.4 - 28 VDC
- Current with No Load (Typical): 149 - 211mA
- Outputs 1-8 Continuous Dutt: 1A or 2A per output based on model, 10A maximum
- Input Terminal Block Ratings: 5mm spacing 14 -28 AWG
- Output Terminal Block Ratings: 5mm spacing 14 -28 AWG
- Note: 1/4" spacing must be maintained between power limited and non power limited wiring , properly size wire based on load
- Main Fuse Rating: 15A for 2A variant, 10A for 1A variant
- Main Fuse Type: mini-ATO
- Caution: For continued protection against risk of fire, replace only with fuse of the same type and having the same electrical ratings.
- Voltage Trigger Isolation: Optical
- End of Line Trigger: Trips +/- 50% of 2.2kΩ
- Transfer Relay Contacts: 10A for 2 Amp variant / 8A for 1A variant
- Trouble Form C Contacts: 120 VAC 3A/30 VDC 3A
- Triggered Form C Contacts: 120 VAC 3A/30 VDC 3A
- Ambient Operating Temperature: +32 to 120F (0 to 49C)
- Note: The unit shall be installed in accordance with the National electrical code, ANSI/NFPA 70; Canadian electrical code, or any other applicable codes
- Note: For UL compliance the unit shall be installed in a suitable enclosure that is listed to UL 603, UL 294, ULC-S318 or ULC-S533.
- Note: Glass fused variants shall either be powered by a UL 294 or 603 or ULC S318 or ULC S533 power supply with a class 2 output or class 1 wiring must be utilized
Specifications for Securitron SMCPDB-8F1R1
Other SpecsAlternate Codes | PDB-8F1R1, PDB8F1R1 |
Category | Access Control, Alarm Power Supplies, Alarms & Intercom, Burglar Alarms, CCTV Products, Power Supplies, Wire & Power Supplies |
Distribution Board | Glass Fused Outputs, Power Distribution Board |
Distribution Output Number | 8 |
Door Application | Power Supplies |
Relay Amperage | 1 Amp Each |
Relay Number | 1 Relay, Fire Alarm Interface |